1P+N C6 RCBO 120-230V 10mA white - 14411.06

Pdf

14411.06
Wiring devices / Traditional wiring devices / PLANA / Devices

1P+N C6 RCBO 120-230V 10mA white
1P+N C 6 residual current breaker with overcurrent protection, supply voltage 120-230 V~ 50-60 Hz, IΔn 10 mA, breaking capacity 1500 A, white - 2 modules

Product Status
3 - Active

Sheets, Manuals, Documentation


Drawings

Class group
Circuit breakers and fuses
Class
Earth leakage circuit breaker
Number of poles (total)
2
Number of protected poles
1
Rated voltage
230 V
Rated current
6 A
Rated fault current
6 A
Leakage current type
A
Current limiting class
1
Rated short-circuit breaking capacity Icn according to EN 61009-1
1.500,00 kA
Surge current capacity
1,50 kA
Voltage type
AC
Frequency
50/60 Hz
Release characteristic
C
Concurrently switching neutral conductor
Yes
Over voltage category
3
Built-in depth
38,00 mm
Flush-mounted installation
Yes
Anti-nuisance tripping version
No
Degree of protection (IP)
IP40
Minimum order quantity: 5 NR

Barcode

Barcode Qty 1 NR
8007352107915
1 NR
6x5.4x5.3 [cm]
97.13 [g]
Barcode Qty 5 NR
8007352107922
5 NR
17.2x13.1x6 [cm]
545.87 [g]
Question: Why is it specified that the differential circuit breaker should not be used as a control 1-way switch?
Answer: The product cannot be used as a control 1-way switch as it is designed to be installed upstream of a socket outlet or of a device for the sole purpose of permitting protection against overloads and the short-circuiting of the device itself and for the protection of the user against contact voltages; it is therefore an intended use that is completely different from that of a classic control 1-way switch, where the power supply interruptions towards the load occur according to the user’s desire.

Didn't find the answer you were looking for?

Ask a question

Share

Codice QR scheda articolo

Legal

Vimar reserves the right to change at any time and without notice the characteristics of the products reported. Installation should be carried out by qualified staff in compliance with the current regulations regarding the installation of electrical equipment in the country where the products are installed. For the terms of use of the information on the product info sheet see Conditions of Use.