If I wired the 02660 emergency light in "emergency only" (SE) mode, can I vary the operation to "always on" (SA) without having to touch the wiring?

Yes, it is possible if the lamp is configured in the By-me control unit. Just modify the relevant parameters in the control unit.

I wired and set the 02660 lamp in the By-me control unit to "always on" (SA), why does it still only work in "emergency only" (SE) mode?

It is set in the control unit to "emergency only". The parameter set in the By-me system has priority over the wiring configuration. Set it to "always on" in the control unit.

I wired the 02660 emergency light in the "emergency only" (SE) mode, but it only flashes twice and doesn't turn on in a power outage, why?

Check that the 2 switches in the battery compartment are set to ON. Selector 1: Enable the battery (battery ON = enabled, 1 = battery is not enabled). Selector 2: Set the lighting time during a power failure (ON=1 hour at 100% brightness, 1 = 3 hours at 30% brightness).

Can I configure the 02660 emergency light in a scenario?

Yes, you can configure the emergency light in a scenario. Through the normal process of creating scenarios, just include the emergency light group and set it to on or off depending on your requirement.

Where can I find the settings of the 02660 emergency light configured in the By-me system?

Where it is grouped, as with all By-me devices. In the Parameters menu, you can set the operation mode (always lit or emergency) and the functional duration in an emergency (1 or 3 hours - the chosen value automatically determines the light intensity).

How do I reset an 02660 emergency light?

It works like any By-me device. You enter Configuration→Reset Management→Device Reset→hold the configuration button down until the configuration LED turns on and then turns off again.

Can I control the 02660 emergency light with a rocker button if configured in the By-me system?

Yes, you can. You just need to configure the rocker button in the same group as the emergency light. This will allow the switch to control the light; the safety function in the event of a blackout is still preserved in any case.

How should I configure the 02660 emergency lights on a By-me control unit?

The emergency lighting part no. 02660 can be configured on a By-me control unit only if it has an appropriate 01846 interface. You have to create a home automation group → Add Device → press and release the configuration button on the light. At this point, the configuration LED of the light will come on for a few seconds and then turn off again.

Do the 02660 emergency lights have to be included in a By-me system group to work?

No, the 02660 emergency lights can be wired in the traditional way and will function without the intervention of the By-me control unit. The lights only have to be configured in a By-me system group only if you are using the appropriate interface part no.01846.